578
9424200994 Rev N
Blinder Angle
Setting Range ........................................................... 1 to 90 degrees
Accuracy....................................................................
±2 degrees
Blinder Traverse Time Delay
Setting Range ........................................................... 0 to 10,000 ms
Accuracy....................................................................
±1.5% or ±4 cycles, whichever is greater
Trip Delay
Setting Range ........................................................... 0 to 5,000 ms
Accuracy....................................................................
±1.5% or ±4 cycles, whichever is greater
Min I1
Setting Range ........................................................... 5 to 600%
Accuracy....................................................................
±2%
I2/I1 Ratio
Setting Range ........................................................... 10 to 200%
Accuracy....................................................................
±1%
78V - Vector Jump Protection
Pickup Setting Range ................................................ 2 to 90 degrees
Pickup Accuracy ........................................................
±1 degree
81 - Frequency Protection
O/U
Pickup
Setting Range ........................................................... 15 to 70 Hz
Accuracy....................................................................
±0.01 Hz
Dropout ...................................................................... 0.02 Hz
±0.01 Hz of the actual pickup value
Time Delay
Setting Range ........................................................... 0 to 600,000 ms
Accuracy....................................................................
±1% or ±2 cycles, whichever is greater, plus 3
cycle recognition time for time delays < 50 ms
ROC
Pickup
Setting Range ........................................................... 0.2 to 20 Hz/sec (positive, negative, or either)
Accuracy....................................................................
±2% or ±0.1 Hz/sec of the setting, whichever is
greater
Dropout ......................................................................
±3% of the actual pickup value
Over/Underfrequency Inhibit
Setting Range ........................................................... 15 to 70 Hz
Increment .................................................................. 0.01 Hz
Accuracy....................................................................
±0.01 Hz
Negative-Sequence Inhibit
Setting Range ........................................................... 0 to 99% of nominal voltage
Accuracy....................................................................
±0.5% or ±1 V, whichever is greater
Time Delay
Setting Range ........................................................... 0 to 600,000 ms
Accuracy....................................................................
±0.5% or ±1 cycle, whichever is greater, plus
recognition time
*
Specifications - 25 Hz Operation