Basler Electric BE1-11g User Manual
Page 170

158
9424200994 Rev N
Setting
Range
Increment
Unit of
Measure
Default
Voltage Source
> Volt Dest
Disabled or Enabled
n/a
n/a
Disabled
Freq Source > Freq Dest
Disabled or Enabled
n/a
n/a
Disabled
Voltage Output Mode
Continuous or Proportional
n/a
n/a
Proportional
Volt Pulse Width
0 or 0.1 to 5
0.1
seconds
0.5
Volt Pulse Interval
0 or 0.2 to 10
0.1
seconds
1
Frequency Output Mode
Continuous or Proportional
n/a
n/a
Proportional
Freq Pulse Width
0 to 99.9
0.1
seconds
5
Freq Pulse Interval
0 to 99.9
0.1
seconds
10
Angle Compensation
0 to 359.9
0.1
degrees
0
VM Live Voltage
0 or 10 to 90
1
percent
0
VM Dead Voltage
0 or 10 to 90
1
percent
0
VM Drop Out Delay
0 or 50 to 60,000
varies
milliseconds
50
Voltage Monitor Logic
0 = Disabled
123, 12, 13, 23
n/a
n/a
0
Synchronizer (25A)
BE1-11g