Setting

Range

Increment

Unit of

Measure

Default

Voltage Source

> Volt Dest

Disabled or Enabled

n/a

n/a

Disabled

Freq Source > Freq Dest

Disabled or Enabled

n/a

n/a

Disabled

Voltage Output Mode

Continuous or Proportional

n/a

n/a

Proportional

Volt Pulse Width

0 or 0.1 to 5

0.1

seconds

0.5

Volt Pulse Interval

0 or 0.2 to 10

0.1

seconds

1

Frequency Output Mode

Continuous or Proportional

n/a

n/a

Proportional

Freq Pulse Width

0 to 99.9

0.1

seconds

5

Freq Pulse Interval

0 to 99.9

0.1

seconds

10

Angle Compensation

0 to 359.9

0.1

degrees

0

VM Live Voltage

0 or 10 to 90

1

percent

0

VM Dead Voltage

0 or 10 to 90

1

percent

0

VM Drop Out Delay

0 or 50 to 60,000

varies

milliseconds

50

Voltage Monitor Logic

0 = Disabled

123, 12, 13, 23

n/a

n/a

0

Synchronizer (25A)

BE1-11g