Basler Electric BE1-11g User Manual
Page 128

116
9424200994 Rev N
Setting
Range
Increment
Unit of
Measure
Default
Flux Balance Pickup
0 or 0.1 to 5
0.01
amps
0
Time Delay
0 to 60,000
varies
milliseconds
0
CT Circuit 1 Tap
Set on the System Parameters,
Transformers Setup screen
n/a
n/a
n/a
CT Circuit 2 Tap
Set on the System Parameters,
Transformers Setup screen
n/a
n/a
n/a
2
nd
Slope Pickup
0 or 0.1 to 20
0.01
n/a
0
Restraint Slope 2
15 to 140
1
percent
45
Slope Alarm
0 or 50 to 100
1
percent
0
Flux Balance Pickup
Alarm
0 or 0.1 to 5
0.01
amps
0
Unrestrained
Tripping Mode
Enabled or Disabled
n/a
n/a
Disabled
Unrestrained
Tripping Pickup
0 to 21
1
n/a
0
Harmonics Mode
Independent or Shared
n/a
n/a
Independent
2
nd
Harmonic
0 or 5 to 75
1
percent
0
5
th
Harmonic
0 or 5 to 75
1
percent
0
Transient Monitor
Operate Time
0 to 10,000
varies
milliseconds
100
Transient Monitor
Delay Time
0 to 10,000
varies
milliseconds
0
0BPhase Current Differential (87) Protection
BE1-11g