Basler Electric BE1-11g User Manual

Page 128

background image

116

9424200994 Rev N

Setting

Range

Increment

Unit of

Measure

Default

Flux Balance Pickup

0 or 0.1 to 5

0.01

amps

0

Time Delay

0 to 60,000

varies

milliseconds

0

CT Circuit 1 Tap

Set on the System Parameters,

Transformers Setup screen

n/a

n/a

n/a

CT Circuit 2 Tap

Set on the System Parameters,

Transformers Setup screen

n/a

n/a

n/a

2

nd

Slope Pickup

0 or 0.1 to 20

0.01

n/a

0

Restraint Slope 2

15 to 140

1

percent

45

Slope Alarm

0 or 50 to 100

1

percent

0

Flux Balance Pickup

Alarm

0 or 0.1 to 5

0.01

amps

0

Unrestrained

Tripping Mode

Enabled or Disabled

n/a

n/a

Disabled

Unrestrained

Tripping Pickup

0 to 21

1

n/a

0

Harmonics Mode

Independent or Shared

n/a

n/a

Independent

2

nd

Harmonic

0 or 5 to 75

1

percent

0

5

th

Harmonic

0 or 5 to 75

1

percent

0

Transient Monitor

Operate Time

0 to 10,000

varies

milliseconds

100

Transient Monitor

Delay Time

0 to 10,000

varies

milliseconds

0

0BPhase Current Differential (87) Protection

BE1-11g