Pickup verification (vx fundamental mode), Timing verification (vx fundamental mode), Pickup verification (vx third harmonic mode) – Basler Electric BE1-11g User Manual
Page 433: Timing verification (vx third harmonic mode)
9424200994 Rev N
421
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
Pickup Verification (Vx Fundamental Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy =
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98%
±1%
Step Pickup Setting
Low
Actual Pickup
High
Low
*
Actual Dropout
High
*
Pass/Fail
6
125.0 V
122.5 V
127.5 V 121.3 V
123.8 V
P / F
7
75.0 V
73.5 V
76.6 V
72.8 V
74.3 V
P / F
7
30.0 V
29.0 V
31.0 V
29.1 V
29.7 V
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (Vx Fundamental Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy =
±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
Pickup Verification (Vx Third Harmonic Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy =
±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98%
±1%
Step Pickup Setting
Low
Actual Pickup
High
Low
*
Actual Dropout
High
*
Pass/Fail
6
125.0 V
122.5 V
127.5 V 121.3 V
123.8 V
P / F
7
75.0 V
73.5 V
76.6 V
72.8 V
74.3 V
P / F
7
30.0 V
29.0 V
31.0 V
29.1 V
29.7 V
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (Vx Third Harmonic Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy =
±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
BE1-11g
Auxiliary Overvoltage (59X) Test