402

9424200994 Rev N

Table 150. Timing Test Settings (Vx Fundamental Mode)

Pickup Setting

Time Delay

115 V

2,000 ms

115 V

5,000 ms

115 V

10,000 ms

Step 2: Prepare to monitor the 27X-1 timings. Timing accuracy is verified by measuring the elapsed

time between a sensing voltage change and OUT1 closing.

Step 3: Connect and apply a 120 Vac, single-phase voltage source to terminals C17 (polarity) and C18

(non-polarity).

Step 4: Step the voltage down to 110 volts. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 150. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 27X-2, 27X-3, and 27X-4.

Pickup Verification (Vx Third Harmonic Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 151 to the BE1-11g. Reset all

targets.

Table 151. Operational Settings (Vx Third Harmonic Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Aux VT Ratio

1

System Parameters, Sensing
Transformers

Sets auxiliary VT ratio to 1

Aux VT
Connection

AN

System Parameters, Sensing
Transformers

Sets auxiliary VT connection to
AN

Element Mode

Vx Third
Harmonic

Protection, Voltage,
Undervoltage (27X-1)

Enables 27X-1 function for Vx
Third Harmonic mode

Inhibit Level

10 V

Protection, Voltage,
Undervoltage (27X-1)

Sets inhibit level to 10 V

Timing Mode

Definite

Protection, Voltage,
Undervoltage (27X-1)

Selects definite timings

27X-1 3RD

Enabled

Target Configuration, Targets

Enables Vx Third Harmonic
target for 27X-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 283.

Blocking is disabled.

OUT1 closes for 27X-1 Trip.

OUT2 closes for 27X-1 Pickup.

Fault recording is enabled.

Auxiliary Undervoltage (27X) Test

BE1-11g