Specifications, Operating power, Analog inputs – Basler Electric BE1-11g User Manual
Page 645: Rtd inputs, Figure 387
9424200994 Rev N
633
Figure 387. RTD Type Selection Screen
Use the Settings Explorer to open the Programmable Outputs, Remote RTD, RTD Block Configuration
tree branch and enter a user-defined name (up to 64 alphanumeric characters) for the RTD Configuration
Block selected. Check the boxes next to the RTDs to include in each configuration group. See Figure 388.
The source for the 49RTD protection elements can be set for RTD Group 1, 2, 3, 4, 5, 6, or 7. Refer to the
Resistance Temperature Detector (49RTD) Protection
chapter for information on setting 49RTD
protection elements.
Figure 388. RTD Configuration Block Screen
Specifications
Operating Power
Nominal ...................................... 125/250 Vac/dc
Range ......................................... 90 to 270 Vac or 90 to 300 Vdc
Maximum Consumption ............. 9 W
Analog Inputs
The RTD module contains four programmable analog inputs.
Rating ......................................... 4 to 20 mAdc or 0 to 10 Vdc (user-selectable)
RTD Inputs
The RTD module contains 12 programmable RTD inputs.
User-Selectable Types ............... 100
Ω Platinum (DIN43760), 10 Ω Copper, 100 Ω Nickel, or 120 Ω Nickel
Range .........................................
–50 to 250°C (–58 to 482°F)
Accuracy.....................................
±2°C (3.6°F)
BE1-11g
RTD Module