beautypg.com

Connections, Terminations, Operating power – Basler Electric BE1-11g User Manual

Page 631: Alarm contacts, Rtd module inputs and outputs

background image

9424200994 Rev N

619

Connections

RTD module connections are dependent on the application. Incorrect wiring may result in damage to the
module.

Note

Be sure that the RTD module is hard-wired to earth ground with no
smaller than 12 AWG (3.31 mm

2

) copper wire attached to the chassis

ground terminal on the module.

Terminations

The terminal interface consists of permanently mounted connectors with screw-down compression
terminals.

RTD module connections are made with one 6-position connector, two 12-position connectors, and two
15-position connectors. Connector screw terminals accept a maximum wire size of 12 AWG (3.31 mm

2

).

Maximum screw torque is 5 inch-pounds (0.56 N

•m) for the 12- and 15-position connectors. Maximum

screw torque is 9 inch-pounds (1.01 N

•m) for the 6-position connector.

Operating Power

The RTD module operating power input accepts 125/250 Vac/dc and tolerates voltage over the range of
90 to 270 Vac or 90 to 300 Vdc. The operating power inputs are not polarity sensitive. Operating power
terminals are listed in Table 254.

Table 254. Operating Power Terminals

Terminal

Description

TB1-1

Operating power input

TB1-2

Operating power input

TB1-3

Chassis ground connection

Alarm Contacts

These terminals provide form C (SPDT) alarm contacts. Alarm contact terminals are listed in Table 255.

Table 255. Alarm Contact Terminals

Terminal

Description

TB1-4

Normally Open

TB1-5

Common

TB1-6

Normally Closed

RTD Module Inputs and Outputs

Input and output terminals are shown in Figure 366 and listed in Table 256.

BE1-11g

RTD Module