Basler Electric BE1-11g User Manual
Page 480

468
9424200994 Rev N
Setting
Value
BESTCOMSPlus Screen
Description
Element Mode
IA
Protection, Current,
Instantaneous Overcurrent (50-1)
Enables 50-1 function for
IA mode
Direction
Forward Protection, Current,
Instantaneous Overcurrent (50-1)
Selects forward direction
for 50-1
Element Mode
3I0
Protection, Current,
Instantaneous Overcurrent (50-2)
Enables 50-2 function for
3I0 mode
Direction
Forward Protection, Current,
Instantaneous Overcurrent (50-2)
Selects forward direction
for 50-2
Element Mode
I2
Protection, Current,
Instantaneous Overcurrent (50-3)
Enables 50-3 function for
I2 mode
Direction
Forward Protection, Current,
Instantaneous Overcurrent (50-3)
Selects forward direction
for 50-3
50-1 67 A
Enabled Target Configuration, Targets
Enables phase A
directional target for 50-1
50-2 67 Residual
Enabled Target Configuration, Targets
Enables residual
directional target for 50-2
50-3 67 Neg SEQ
Enabled Target Configuration, Targets
Enables Neg SEQ
directional target for 50-3
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 306.
•
Blocking is disabled.
•
OUT1 closes for 50-1 Trip.
•
OUT2 closes for 50-2 Trip
•
OUT3 closes for 30-3 Trip.
•
Fault recording is enabled for 50-1, 50-2, and 50-3.
Figure 306. BESTlogicPlus Settings
Step 3: Using Table 213 as a guide, send the settings to the BE1-11g. Prior to each directional test,
reset the BE1-11g targets from the previous test. Max Torque Angle setting, for positive and
Directional Overcurrent (67) Test
BE1-11g