Settings, Tap compensation settings, N figure 70 β Basler Electric BE1-11g User Manual
Page 125: Table 39
9424200994 Rev N
113
Figure 70. Phase Current Differential Element Logic Block
Table 39. Logic Inputs and Outputs
Name
Function
Purpose
Block
Input
Disables the 87 function when true
Trip
Output
True when the 87 element is in a trip condition
Pickup
Output
True when the 87 element is in a pickup condition
Unrestrained Trip
Output
True when the 87 element is in an unrestrained trip condition
2
nd
Harmonic Inhibit
Output
True when the 87 is inhibited by 2
nd
harmonic ratio
5
th
Harmonic Inhibit
Output
True when the 87 is inhibited by 5
th
harmonic ratio
Settings
Tap Compensation Settings
The measured currents must be tap adjusted to eliminate magnitude mismatch prior to being used by the
Phase Current Differential Protection (87) element. The tap adjust factors can be manually calculated per
Equation 13. Or, the user can enter the MVA and kV base parameters (Table 40) and the BE1-11g will
calculate the tap-adjust factors using CT Ratio (CTR) and Compensation Factor (COMP) parameters from
the current measurement input function settings. For a transformer application, the mismatch will be at a
minimum if the actual transformer voltage ratings are used.
ππ΄ππ =
πππ΄ Γ 1000 Γ πΆππππ
β3 Γ πππ Γ πΆππ π
Equation 13. Calculate Tap Adjust Factors
Table 40. MVA and kVn Base Parameters
Parameter
Description
Explanation
Tapn
Restraint winding
The BE1-11g has 2 restraint windings (2 taps).
MVA
MVA base
Full load MVA or top rating of the protected equipment.
kVn
kV base for CT input n
L-L Voltage in kV for each CT input circuit.
CTRn
CT ratio for CT input n
Actual ratio not effective ratio.
COMPn
Phase compensation
adjustment factor for
CT input n
β3 if CTs are connected in Delta (CTcon = DAB or DAC).
1 in all other cases.
See the
chapter.
The input currents can be tap adjusted up to a spread ratio of 10:1. If the ratio between TAP1 and TAP2
is greater than ten, it will be necessary to adjust the CT ratios to bring the tap factors closer together.
When the auto-tap calculation feature is used, the BE1-11g will give an error message if the spread ratio
is greater than ten.
BE1-11g
0BPhase Current Differential (87) Protection