Remote analog outputs configuration, Configuration settings, O figure 385 – Basler Electric BE1-11g User Manual

Page 643

background image

9424200994 Rev N

631

Figure 385. Module 1 Input #1 Screen

Table 257 summarizes the configuration settings for remote analog inputs.

Table 257. Configuration Settings for Remote Analog Inputs

Setting

Range

Increment

Unit of Measure

Default

Label

Up to 64 alphanumeric characters

n/a

n/a

Module 1

Input 1

Type

Voltage or Current

n/a

n/a

Voltage

Param Min

–99,999.9 to 99,999.9

0.1

n/a

–99,999.9

Param Max

–99,999.9 to 99,999.9

0.1

n/a

–99,999.9

Min Input Current

4 to 20

0.01

milliamps

4

Max Input Current

4 to 20

0.01

milliamps

20

Min Input Voltage

0 to 10

0.01

volts

0

Max Input Voltage

0 to 10

0.01

volts

10

Remote Analog Outputs Configuration

The RTD module provides four analog outputs. The BE1-11g supports two RTD modules at once.

Configuration Settings

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Outputs, Remote Analog Outputs

HMI Navigation Path: Settings Explorer, Analog Outputs

Configuration settings are made using the BE1-11 plugin for BESTCOMSPlus. To program the
configuration settings, use the Settings Explorer to open the Programmable Outputs, Remote Analog
Outputs tree branch and select the module and output to be modified. Refer to Figure 386. Use the drop-
down menu under Param Selection to select a parameter. Select the Output Type. The analog outputs
are always monitored and their status is displayed on the appropriate metering screens. The BE1-11g
reports Out of Range when an RTD module is disconnected.

Ranges must be set for the selected output type. Param Min correlates to Min Output Current or Min
Output Voltage and Param Max correlates to Max Output Current or Max Output Voltage.

BE1-11g

RTD Module