Functional test report, Alarm verification, Inverse time pickup verification – Basler Electric BE1-11g User Manual

Page 395: Definite time pickup verification, N table 131

background image

9424200994 Rev N

383

Table 131. Definite Time Verification Test Settings

Setting

Value

Description

Inverse Time Pickup

0

Disables Inverse Time Pickup

Definite Timer 1 Pickup

2.36

Sets Definite Timer 1 Pickup at 118% of nominal (2.36 V/Hz)

Definite Timer 1 Time Delay

500

Sets Definite Timer 1 Time Delay at 500 ms

Alarm Pickup

0

Disables Alarm Pickup

Step 2: Connect and apply 120 Vac, three-phase, 60-hertz voltage source to Terminals C13 (A-phase),

C14 (B-phase), C15 (C-phase), and C16 (neutral).

Step 3: Step the A-phase voltage to 142.2 V (118.5% or 2.37 V/Hz). Measure the time between the

increase in voltage and the closure of OUT1. Record the result.

Step 4: Repeat steps 1 through 3 for Time Delays of 1 second and 5 seconds. Record the results.

Step 5: (Optional.) Repeat steps 1 through 4 for the B-phase and C-phase voltage inputs.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Set Definite Timer 1 Pickup to 0 and Definite Timer 2 Pickup to 2.36 V/Hz and repeat

steps 1 through 6 for Definite Timer 2.

Functional Test Report

Alarm Verification

Alarm Setting Range = 0.5 to 6 V/Hz

Alarm Accuracy =

±2% or ±0.05 V/Hz, whichever is greater

Alarm/Reset Ratio = 98%

±1%

Step

Alarm

Setting

Low

Actual

Alarm

High

Low

*

Actual

Reset

High

*

Pass/Fail

6

2.05

2.00 V/Hz

2.10 V/Hz

1.94 V/Hz

1.98 V/Hz

P / F

* Reset range is calculated from the alarm setting and may need adjusted based on actual alarm.

Inverse Time Pickup Verification

Pickup Setting Range = 0.5 to 6 V/Hz

Pickup Accuracy =

±2% or ±0.05 V/Hz, whichever is greater

Dropout/Pickup Ratio = 98%

±1%

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

7

2.10

2.05 V/Hz

2.15 V/Hz

2.037 V/Hz

2.079 V/Hz

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Definite Time Pickup Verification

Pickup Setting Range = 0.5 to 6 V/Hz

Pickup Accuracy =

±2% or ±0.05 V/Hz, whichever is greater

Dropout/Pickup Ratio = 98%

±1%

BE1-11g

Overexcitation (24) Test