Step 8: Slowly decrease the line voltage until the 25A Volt Diff digital point turns off. This should happen

at 58.89 V

±1 V. Record the result.

Step 9: Increase the voltage until the 25A Volt Diff digital point turns on (69.28 V). Record the result.

Step 10: (Optional) Repeat steps 2 through 9 for Settings Group 1, 2, and 3.

Slip Frequency Verification

Step 1: Use BESTCOMSPlus to monitor the status of 25A Slip Diff in Metering Explorer, Status, Digital

Points (1536-1567).

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). The 25A Slip Diff

digital point should light in BESTCOMSPlus.

Step 3: Slowly increase the frequency of the phase voltage source until the 25A Slip Diff turns off. This

should occur at 60.106 Hz

±0.01 Hz. Record the results.

Step 4: Decrease the frequency of the phase voltage source until the 25A Slip Diff turns on around

60.1 Hz

±0.01 Hz.

Step 5: Slowly decrease the frequency of the phase voltage source until the 25A Slip Diff turns off. This

should happen below 60.0008 Hz

±0.01 Hz since the Freq Source > Freq Destination setting is

enabled.

Step 6: (Optional.) Repeat Steps 2 through 5 for Settings Group 1, 2, and 3.

Voltage Source > Voltage Destination Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT6.

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28

∠0° Vpn to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT6 should

close.

Step 3: Slowly increase the phase voltage source until OUT6 opens. This should occur at 69.63 V

±1 V.

Step 4: (Optional.) Repeat Steps 2 and 3 for Settings Group 1, 2, and 3.

Frequency Source > Frequency Destination Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT6.

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT6 should be

open.

Step 3: Slowly increase the frequency of the phase voltage source until OUT6 closes. This should occur

at 60.0008 Hz.

Step 4: (Optional.) Repeat Steps 2 and 3 for Settings Group 1, 2, and 3.

Voltage Raise/Lower Proportional Output Verification

Step 1: Use BESTCOMSPlus to monitor the status of OUT4 (Lower) and OUT5 (Raise).

Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11g terminals C13

(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,

∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT4 and OUT5

should be open.

BE1-11g

Synchronizer (25A) Test