152
9424200994 Rev N
Table 58. Common System and Sensing Transformer Combinations
Phase VT
Connection
Phase
Rotation
Aux VT
Connection
Secondary
Phase Voltage
(Phase-Neutral)
Secondary
Aux Voltage
Angle
Compensation
3-wire
ABC
AB
69.3
120
0
°
3-wire
ABC
BC
69.3
120
240
°
3-wire
ABC
CA
69.3
120
120
°
3-wire
ACB
AB
69.3
120
0
°
3-wire
ACB
BC
69.3
120
120
°
3-wire
ACB
CA
69.3
120
240
°
4-wire
ABC
AN
69.3
69.3
0
°
4-wire
ABC
BN
69.3
69.3
240
°
4-wire
ABC
CN
69.3
69.3
120
°
4-wire
ABC
AB
69.3
120
30
°
4-wire
ABC
BC
69.3
120
270
°
4-wire
ABC
CA
69.3
120
150
°
4-wire
ACB
AN
69.3
69.3
0
°
4-wire
ACB
BN
69.3
69.3
120
°
4-wire
ACB
CN
69.3
69.3
240
°
4-wire
ACB
AB
69.3
120
330
°
4-wire
ACB
BC
69.3
120
90
°
4-wire
ACB
CA
69.3
120
210
°
AB
ABC
AB
69.3
120
0
°
AB
ACB
AB
69.3
120
0
°
BC
ABC
BC
69.3
120
0
°
BC
ACB
BC
69.3
120
0
°
AB
ABC
BC
69.3
120
240
°
AB
ACB
BC
69.3
120
120
°
AB
ABC
AN
69.3
69.3
330
°
AB
ACB
AN
69.3
69.3
30
°
Mode
Two operating modes are available: Phase Lock Loop and Anticipatory. In both modes, the BE1-11g
adjusts the frequency and voltage of the generator to match that of the bus (mains) at the proper relative
phase angle, and then connects the generator to the bus by closing the breaker. Anticipatory mode has
the added capability of compensating for the breaker closing time (the delay between when a breaker
close command is issued and the breaker contacts close). The BE1-11g controls the slip frequency
difference between the generator and the bus, and then calculates the advance angle that is required to
compensate for the breaker closure time.
Synchronization is accomplished using the Raise and Lower logic outputs for the voltage and frequency.
These logic outputs can be set to continuous or proportional. Continuous mode turns the required logic
output on until either it is in the synchronization window or overshoots it. Proportional mode toggles the
contacts based on the respective Pulse Width setting, Pulse Interval setting, and calculated error.
Synchronizer (25A)
BE1-11g