Een (figure 47), N table 18 – Basler Electric BE1-11g User Manual
Page 74
![background image](https://www.manualsdir.com/files/773770/content/doc074.png)
62
9424200994 Rev N
Figure 47. Auxiliary Undervoltage Settings Screen
Table 18. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
*
Disabled,
3V0, V1, V2,
Vx Fundamental,
Vx Third Harmonic
n/a
n/a
Disabled
Pickup
0 or 1 to 150
0.1
volts
0
Inhibit Level
0 or 1 to 150
0.1
volts
0
Timing Mode
Definite or Inverse
n/a
n/a
Definite
Time Delay (Definite Timing)
50 to 600,000
varies
milliseconds
50
Time Dial (Inverse Timing)
0 to 9.9
0.1
units
0
* To use 3V0, V1, or V2, the VTP connection cannot be single-phase.
Auxiliary Undervoltage (27X) Protection
BE1-11g