25 - sync-check protection, 25a - synchronizer – Basler Electric BE1-11g User Manual
Page 565

9424200994 Rev N
553
Alarm
Pickup
Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................
±2% or ±0.05 V/Hz, whichever is greater
Reset/Alarm Ratio ..................................................... 98%
±1%
Time Delay
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................
±0.5% or ±3 cycles, whichever is greater
25 - Sync-Check Protection
Settings
Voltage Difference
Setting Range ........................................................... 0 to 50% of nominal
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Slip Angle
Setting Range ........................................................... 1 to 99
°
Accuracy....................................................................
±1°
Slip Frequency
Setting Range ........................................................... 0.01 to 0.50 Hz
Accuracy....................................................................
±0.01 Hz
Sensing
Angle Compensation Setting Range ......................... 0 to 359.9
°
Voltage Monitoring
Live/Dead Voltage
Setting Range ........................................................... 0 to 90%
Accuracy....................................................................
±2%
Drop Out Delay
Setting Range ........................................................... 50 to 60,000 ms
Accuracy....................................................................
±0.5% or ±2 cycles, whichever is greater
25A - Synchronizer
Settings
Voltage Difference
Setting Range ........................................................... 2 to 15% of nominal
Accuracy....................................................................
±2% or ±1 V, whichever is greater
Slip Frequency
Setting Range ........................................................... 0 to 0.5 Hz
Accuracy....................................................................
±0.01 Hz
Breaker Close Angle
Setting Range ........................................................... 3 to 20 degrees
Accuracy....................................................................
±1 degree
Breaker Close Time
Setting Range ........................................................... 0 to 1,000 ms
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
Sync Fail Activation Delay
Setting Range ........................................................... 0.1 to 600 seconds
Accuracy....................................................................
±1% or ±3 cycles, whichever is greater
BE1-11g
Specifications