beautypg.com

Harmonics, Unrestrained tripping, Programmable alarm – Basler Electric BE1-11g User Manual

Page 124: Element blocking, Logic connections

background image

112

9424200994 Rev N

Harmonics

The second and fifth harmonic functions check the ratio of the second and fifth harmonic operate current
to the fundamental operate current. Traditional harmonic restraint units operate on the ratio of harmonic
current to total operate current versus the ratio to only the fundamental operate current used by the
BE1-11g. For this reason, the BE1-11g will provide greater security for inrush and overexcitation with the
same harmonic inhibit ratio settings used with traditional differential relays. When either of these two
comparators is above the threshold, the percentage-restrained output is blocked from setting the
Restrained Trip logic output. If the second or fifth harmonic inhibit comparators are picked up for any of
the three phases, the Second Harmonic Inhibit and Fifth Harmonic Inhibit logic outputs respectively are
also set.

In many cases, the second harmonic content of the inrush current may show up primarily in only one or
two phases, which can cause one or two phases to not be inhibited. The BE1-11g allows the second
harmonic currents to be shared between the three phases. When second harmonic sharing is enabled,
the magnitude of the second harmonic operating current is summed from all three phases and this
magnitude is used by the second harmonic comparator for each phase instead of the second harmonic
operate current for only that phase. This is superior to other methods of cross blocking since each phase
element operates independently in its comparison of operating current to harmonic current. Thus, security
is enhanced without sacrificing dependability because a faulted phase will not be restrained by inrush on
unfaulted phases as is the case with cross blocking schemes.

Unrestrained Tripping

The 87 element provides high-speed tripping for high-grade faults inside the zone of protection. If the
operate current is above the Unrestrained Tripping threshold for any of the three phases, the
Unrestrained Trip logic output becomes true. The transient monitor function also enhances security for
this function by doubling the pickup threshold when CT saturation is detected. The minimum setting for
the Unrestrained Tripping threshold should be the maximum inrush current with a small margin.

Programmable Alarm

An 87 Alarm condition is indicated when the percentage restrained differential protection is nearing a trip
condition on load. This alarm triggers a diagnostic routine that attempts to determine the source of the
mismatch that is causing the differential unbalance.

The alarm appears on the front-panel display, web page interface, and on the Alarms metering screen in
BESTCOMSPlus. Refer to the

Alarms

chapter for information on how to program alarms.

Element Blocking

The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. Connect the
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Phase-current, differential-element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The phase-current, differential-element logic block is illustrated in Figure 70. Logic
inputs and outputs are summarized in Table 39.

0BPhase Current Differential (87) Protection

BE1-11g