beautypg.com

Voting, Element blocking, Logic connections – Basler Electric BE1-11g User Manual

Page 156: Operational settings

background image

144

9424200994 Rev N

annunciate the condition and to initiate corrective action. If a target is enabled for the element, the
BE1-11g will record a target when the Trip output becomes true. See the

Fault Reporting

chapter for more

information about target reporting.

Voting

The Voting parameter defines the number of RTDs in the group that must exceed the pickup setting to
cause a trip. For example, if the 49RTD-1 Voting setting is three, then at least 3 RTDs in the selected
group must exceed the pickup setting to cause a trip.

Element Blocking

The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip and Pickup outputs to logic 0 and resetting the element timer. Connect the
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Remote RTD input element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The remote RTD input element logic block is illustrated in Figure 91. Logic inputs and
outputs are summarized in Table 54.

Figure 91. Remote RTD Input Element Logic Block

Table 54. Logic Inputs and Outputs

Name

Function

Purpose

Block

Input

Disables the 49RTD function when true

Trip

Output

True when the 49RTD element is in trip condition

Pickup

Output

True when the 49RTD element is in pickup condition

Operational Settings

Remote RTD input element operational settings are configured on the Resistance Temperature Detector
settings screen (Figure 92) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 55.

Resistance Temperature Detector (49RTD) Protection

BE1-11g