Output contacts, Contact-sensing inputs – Basler Electric BE1-11g User Manual

Page 576

background image

564

9424200994 Rev N

Output Contacts

Make and Carry for Tripping Duty ............................. 30 A for 0.2 seconds per IEEE Std C37.90-2005 -

IEEE Standard for Relays and Relay Systems
Associated with Electric Power Apparatus
;

7 A continuous AC or DC

Break Resistive or Inductive ...................................... 0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)

Terminals
OUT 1 ........................................................................ C1, C2
OUT 2 ........................................................................ C3, C4
OUT 3 ........................................................................ C5, C6
OUT 4 ........................................................................ C7, C8
OUT 5 ........................................................................ C9, C10
OUT 6 (Optional) ....................................................... E11, E12
OUT 7 (Optional) ....................................................... E9, E10
OUT 8 (Optional) ....................................................... E7, E8
OUT A ....................................................................... C11, C12

Contact-Sensing Inputs

Maximum Input Voltage

The maximum input voltages are the highest voltage for each power-supply range listed under the Power
Supply
section.

Turn-On Voltage

Contact-sensing turn-on voltages are listed in Table 249.

Table 249. Contact-Sensing Turn-On Voltages

Style Option

Nominal Input Voltage

Contact-Sensing Turn-On Voltage

*

Jumper Installed

(Low Position)

Jumper Not Installed

(High Position)

Gxx1xxxxxxxxxx

48 Vdc or 125 Vac/dc

26 to 38 Vdc

69 to 100 Vdc

56 to 97 Vac

Gxx2xxxxxxxxxx

125/250 Vac/dc

69 to 100 Vdc

56 to 97 Vac

138 to 200 Vdc
112 to 194 Vac

Gxx3xxxxxxxxxx

24 Vdc

n/a

Approx. 5 Vdc

* AC voltage ranges are calculated using the default recognition time (4 ms) and debounce time (4 ms).

† Voltage ranges depend on jumper configurations. See the

Contact Inputs and Outputs

chapter for more

information.

Input Burden

Burden values shown in Table 250 assume nominal value of input voltage applied.

Table 250. Contact-Sensing Input Burden

Style Option

Nominal Input Voltage

Burden

Jumper Installed

(Low Position)

Jumper Not Installed

(High Position)

Gxx1xxxxxxxxxx

48 Vdc or 125 Vac/dc

22 k

53 k

Gxx2xxxxxxxxxx

125/250 Vac/dc

66 k

123 k

Gxx3xxxxxxxxxx

24 Vdc

n/a

6 k

Specifications

BE1-11g