Target settings – Basler Electric BE1-11g User Manual

Page 207

background image

9424200994 Rev N

195

Target

Description

59X-#-3V0

Auxiliary Overvoltage, 3V0-3ph VT

59X-#-V1

Auxiliary Overvoltage, Positive-Sequence

59X-#-V2

Auxiliary Overvoltage, Negative-Sequence

59X-#-AUX

Auxiliary Overvoltage, Fundamental VX

59X-#-3RD

Auxiliary Overvoltage, 3

rd

Harmonic VX

60FL

Fuse Loss Detection

62-#

Timer Output

78OOS

Out of Step

78V

Vector Shift

81-#-Over

Frequency, Over

81-#-Under

Frequency, Under

81-#-ROC

Frequency, Rate of Change

86-#

Lockout Function

87-A/B/C

Differential Current, Phase A, B, or C

87-Unrestrained A/B/C

87 Unrestrained, Phase A, B, or C

87N-1

Neutral Current Differential

Analog In #

Remote Analog Input

Target logging for a protective function can be disabled if the function is used in a supervisory or
monitoring capacity. The following paragraphs describe how the BE1-11g is programmed to define which
protective functions log targets.

Target Settings

Targets are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Target Configuration
tree branch. You can select which protective elements trigger a target by selecting Enabled or Disabled
from the Mode drop-down menu next to the targets. See Figure 136.

Figure 136. Target Settings Screen

BE1-11g

Fault Reporting