Target settings – Basler Electric BE1-11g User Manual
Page 207
![background image](https://www.manualsdir.com/files/773770/content/doc207.png)
9424200994 Rev N
195
Target
Description
59X-#-3V0
Auxiliary Overvoltage, 3V0-3ph VT
59X-#-V1
Auxiliary Overvoltage, Positive-Sequence
59X-#-V2
Auxiliary Overvoltage, Negative-Sequence
59X-#-AUX
Auxiliary Overvoltage, Fundamental VX
59X-#-3RD
Auxiliary Overvoltage, 3
rd
Harmonic VX
60FL
Fuse Loss Detection
62-#
Timer Output
78OOS
Out of Step
78V
Vector Shift
81-#-Over
Frequency, Over
81-#-Under
Frequency, Under
81-#-ROC
Frequency, Rate of Change
86-#
Lockout Function
87-A/B/C
Differential Current, Phase A, B, or C
87-Unrestrained A/B/C
87 Unrestrained, Phase A, B, or C
87N-1
Neutral Current Differential
Analog In #
Remote Analog Input
Target logging for a protective function can be disabled if the function is used in a supervisory or
monitoring capacity. The following paragraphs describe how the BE1-11g is programmed to define which
protective functions log targets.
Target Settings
Targets are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Target Configuration
tree branch. You can select which protective elements trigger a target by selecting Enabled or Disabled
from the Mode drop-down menu next to the targets. See Figure 136.
Figure 136. Target Settings Screen
BE1-11g
Fault Reporting