Pickup verification (i2 mode) – Basler Electric BE1-11g User Manual
Page 468
![background image](https://www.manualsdir.com/files/773770/content/doc468.png)
456
9424200994 Rev N
Pickup Verification (I2 Mode)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 204 to the BE1-11g. Reset all
targets.
Table 204. Operational Settings (I2 Mode)
Setting
Value
BESTCOMSPlus Screen
Description
Phase CT
Ratio
1
System Parameters, Sensing
Transformers
Sets phase CT ratio to 1
Element
Mode
I2
Protection, Current, Instantaneous
Overcurrent (51-1)
Enables 51-1 function for I2
mode
Source
CT Circuit 1
Protection, Current, Instantaneous
Overcurrent (51-1)
Selects CT circuit 1 as the
source
51-1 Neg
SEQ
Enabled
Target Configuration, Targets
Enables Neg SEQ target
for 51-1
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 304.
•
Blocking is disabled.
•
OUT1 closes for 51-1 Trip.
•
OUT2 closes for 51-1 Pickup.
•
Fault recording is enabled.
Figure 304. BESTlogicPlus Settings (I2 Mode)
Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and
send the low range test settings (minimum pickup setting) to the BE1-11g for your sensing input
type in Table 205.
Table 205. Pickup Test Settings (I2 Mode)
Sensing Input
Type
Range
Pickup Setting
Time Dial
Time Curve
5 A
Low
0.5 A
0
I2
Middle
5.0 A
0
I2
High
9.0 A
0
I2
1 A
Low
0.1 A
0
I2
Middle
1.0 A
0
I2
High
1.8 A
0
I2
Step 4: Prepare to monitor the 51-1 function operation. Operation can be verified by monitoring OUT2
Step 5: Connect a current source to terminals D1 and D2 (A-phase). For a single-phase input test, I2 =
Ia / 3. Therefore, the BE1-11g should pick up at a value of three times the setting value when
applying only a single-phase input. For example, to determine the pickup current value required
Inverse Overcurrent (51) Test
BE1-11g