beautypg.com

Phase ac voltage inputs, Auxiliary ac voltage input, Analog to digital converter – Basler Electric BE1-11g User Manual

Page 575: Power supply

background image

9424200994 Rev N

563

Terminals (CT1)
IA1 ............................................................................. D1, D2
IB1 ............................................................................. D3, D4
IC1 ............................................................................. D5, D6
IN1 ............................................................................. D7, D8

Terminals (CT2) (Optional)
IA2 ............................................................................. F1, F2
IB2 ............................................................................. F3, F4
IC2 ............................................................................. F5, F6
IN2 ............................................................................. F7, F8

Phase AC Voltage Inputs

Continuous Rating ..................................................... 300 V, Line to Line
One Second Rating ................................................... 600 V, Line to Neutral
Burden ....................................................................... <1 VA @ 300 Vac

Terminals
VA .............................................................................. C13
VB .............................................................................. C14
VC ............................................................................. C15
N ................................................................................ C16

Auxiliary AC Voltage Input

Continuous Rating ..................................................... 150 V, Line to Line
One Second Rating ................................................... 600 V, Line to Neutral
Burden ....................................................................... <1 VA @ 150 Vac
Terminals................................................................... C17, C18

Analog to Digital Converter

Type .......................................................................... 16-bit
Sampling Rate ........................................................... 32 samples per cycle, adjusted to input frequency

(10 to 125 Hz)

Power Supply

Terminals................................................................... A6, A7

Option 1 (48/125 Vac/dc)
DC Operating Range ................................................. 35 to 150 Vdc
AC Operating Range ................................................. 55 to 135 Vac

Option 2 (125/250 Vac/dc)
DC Operating Range ................................................. 90 to 300 Vdc
AC Operating Range ................................................. 90 to 270 Vac

Option 3 (24 Vdc)
Operating Range ....................................................... 17 to 32 Vdc (down to 8 Vdc momentarily)

Frequency Range
Options 1 and 2 only ................................................. 40 to 70 Hz

Burden (Options 1, 2, and 3)
H and P Type Case ................................................... 10 W continuous, 12 W maximum with all outputs

energized

J Type Case .............................................................. 12 W continuous, 14 W maximum with all outputs

energized

BE1-11g