Basler Electric BE1-11g User Manual
Page 500
488
9424200994 Rev N
Setting
Value
BESTCOMSPlus Screen
Description
Circuit 1 Ground
Compensation
No
System Parameters, Transformer
Setup
Disables the primary
winding zero sequence
trap
(Optional) Circuit
1 Diff. Circuit
Primary
System Parameters, Transformer
Setup
Establishes circuit 1 on the
primary side of the
transformer. For report
labeling purposes only.
Circuit 1 Polarity
Normal
System Parameters, Transformer
Setup
Sets the phase rotation of
circuit 1 for ABC
Circuit 1 Phase
Relationship
A
System Parameters, Transformer
Setup
Sets A-phase in circuit 1
equal to the phase
relationship setting for
circuit 2
Mode
Enabled
Protection, Current, Neutral
Differential (87N-1)
Enables the neutral
differential element
Iop Minimum (A)
2.00
Protection, Current, Neutral
Differential (87N-1)
Sets the minimum operate
current required for pickup
to 2 A
Time Delay (ms)
100
Protection, Current, Neutral
Differential (87N-1)
Sets the time to trip after a
pickup to 100 ms
Overcorrection
Coefficient
1.30
Protection, Current, Neutral
Differential (87N-1)
Sets the sensitivity of the
directional sensing by
using a factor of 1.30
CT Flip
No
Protection, Current, Neutral
Differential (87N-1)
Stipulates that IG is in
phase with 3I0 for internal
faults
CT Source
CT1, IG1
Protection, Current, Neutral
Differential (87N-1)
Sets the differential zone
with CT1 and IG1
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 309.
•
Blocking is disabled.
•
OUT1 closes for 87N-1 Trip.
•
OUT2 closes for 87N-1 Pickup.
•
Fault recording is enabled.
Figure 309. BESTlogicPlus Settings
Step 3: Prepare to monitor the 87N-1 function operation. Operation can be verified by monitoring OUT2
Step 4: Connect a single-phase 60-Hz current source to terminals D1 and D2 (CT1 A-phase): 3.0 A
∠0°. Connect a single-phase current source to terminals D7 and D8 (IG input): 3.0 A ∠180°.
Verify that Iop is around zero amps.
Neutral Current Differential (87N) Test
BE1-11g