Anticipatory Functional Test Procedure

Voltage Difference Test (

ΔV)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 236 to the BE1-11g. Reset all

targets.

Table 236. Operational Settings Anticipatory (25A)

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT Ratio

1

System Parameters,
Sensing Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters,
Sensing Transformers

Sets phase VT connection to 4W-Y

27/59 Mode

PN

System Parameters,
Sensing Transformers

Sets 27/59 mode to phase-neutral

Aux VT Ratio

1

System Parameters,
Sensing Transformers

Sets auxiliary VT ratio to 1

Aux VT
Connection

AN

System Parameters,
Sensing Transformers

Sets auxiliary VT connection to AN

Nominal Phase
Voltage

69.3 V

System Parameters, Power
System

Sets nominal phase voltage to
69.3 V

Nominal Aux
Voltage

69.3 V

System Parameters, Power
System

Sets nominal auxiliary voltage to
69.3 V

Element Mode

Anticipatory

Control, Synchronizer (25A)

Enables 25A function for PLL
operation

Voltage
Difference (%)

15.0

Control, Synchronizer (25A)

Sets the voltage difference
requirement to 15% of the nominal
setting

Slip Freq (Hz)

0.1

Control, Synchronizer (25A)

Sets the allowable slip angle to
0.1 Hz

Breaker Close
Time (ms)

800

Control, Synchronizer (25A)

Sets the time it takes the breaker to
close to 800 milliseconds

Breaker Close
Attempts

1

Control, Synchronizer (25A)

Sets number of breaker close
attempts to 1

Sync Fail
Activation Delay
(s)

5.0

Control, Synchronizer (25A)

Sets the activation delay for the
sync fail alarm to 5 seconds

Voltage Source
> Volt Dest

Control, Synchronizer (25A)

Requires voltage at the phase
terminals to be greater than the
voltage at the Vx terminals by 0.5%

Freq Source >
Freq Dest

Control, Synchronizer (25A)

Requires frequency at the phase
terminals to be 0.0008 Hz greater
than the frequency at the Vx
terminals

Voltage Output
Mode

Proportional

Control, Synchronizer (25A)

Sets the voltage control output
mode to proportional

Volt Pulse Width
(s)

5.0

Control, Synchronizer (25A)

Sets the maximum correctional
pulse width for voltage control to 5
seconds

BE1-11g

Synchronizer (25A) Test