beautypg.com

Csa certification, Gost-r certification, Halt (highly accelerated life testing) – Basler Electric BE1-11g User Manual

Page 580: Dnp certification, Iec 61850 certification, Physical

background image

568

9424200994 Rev N

Standards used for evaluation:

UL 508

ISA 12.12.01

CSA C22.2 No. 213-M1987

Warning! - EXPLOSION HAZARD

Do not disconnect equipment unless power has been switched off or
the area is known to be non-hazardous.

Substitution of components may impair suitability for Class 1,
Division 2.

Do not engage USB unless power has been switched off or the area is
known to be non-hazardous.

CSA Certification

This product was tested and has met the certification requirements for industrial control equipment.

Standards used for evaluation:

CSA C22.2 No. 14

GOST-R Certification

GOST-R certified per the relevant standards of Gosstandart of Russia.

HALT (Highly Accelerated Life Testing)

Basler Electric uses HALT to prove that our products will provide the user with many years of reliable
service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate years of
operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible design
elements that will add to the life of this device. As an example of some of the extreme testing conditions,
the BE1-11g was subjected to temperature extremes of –80

°C to +130°C,

vibration extremes of 5 to 45 G

at +20

°C, and temperature/vibration extremes of 45 G over a temperature range of –60°C to +110°C.

Combined temperature and vibration testing at these extremes proves that the BE1-11g is expected to
provide long-term operation in a rugged environment. Note that the vibration and temperature extremes
listed in this paragraph are specific to HALT and do not reflect recommended operation levels. These
operational ratings are listed under Temperature.

DNP Certification

DNP3-2009, V2.6 compliant, Subset Level 2, by Advanced Control Systems, Inc.

IEC 61850 Certification

KEMA certified per IEC 61850 Certificate Level A.

Physical

IP Class ..................................................................... IP50
Case Size .................................................................. Refer to the

Mounting

chapter.

Weight

H1 Rack Mount (H Type Case) ................................. 5.9 lb (2.6 kg)
H1 Panel Mount (P Type Case) ................................ 6.2 lb (2.8 kg)
Vertical Case (J Type Case) ..................................... 5.1 lb (2.3 kg)

Specifications

BE1-11g