Reverse tripping direction (overpower), Forward tripping direction (underpower), Reverse tripping direction (underpower) – Basler Electric BE1-11g User Manual
Page 507
9424200994 Rev N
495
Step Pickup Setting
Low
Actual Pickup
High
Low
*
Actual Dropout
High
*
Pass/Fail
3
500 W
485 W
515 W
475 W
495 W
P / F
5
1,000 W
970 W
1,030 W
950 W
990 W
P / F
5
2,000 W
1940 W
2,060 W 1900 W
1,980 W
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Reverse Tripping Direction (Overpower)
Pickup Setting Range = 1 to 6,000 Watts for 5A sensing
1 to 1,200 Watts for 1A sensing
Pickup Accuracy =
±3 or ±2 W, whichever is greater
Dropout should occur between 95-99% of the actual pickup value.
Step
Pickup Setting
Low
Actual Pickup
High
Low
*
Actual Dropout
High
* Pass/Fail
3
500 W
485 W
515 W
475 W
495 W
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Forward Tripping Direction (Underpower)
Pickup Setting Range = 1 to 6,000 Watts for 5A sensing
1 to 1,200 Watts for 1A sensing
Pickup Accuracy =
±3 or ±2 W, whichever is greater
Reset should occur between 95-99% of the actual pickup value.
Step
Setting
Low
Pickup
High
Low
*
Dropout
High
*
Pass/Fail
3
500 W
485.0 W
515.0 W
475.0 W
495.0 W
P / F
5
250 W
242.5 W
257.5 W
237.5 W
247.5 W
P / F
5
50 W
48.5 W
51.5 W
47.5 W
49.5 W
P / F
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Reverse Tripping Direction (Underpower)
Pickup Setting Range = 1 to 6,000 Watts for 5A sensing
1 to 1,200 Watts for 1A sensing
Pickup Accuracy =
±3 or ±2 W, whichever is greater
Reset should occur between 95-99% of the actual pickup value.
Step
Pickup Setting
Low
Actual Pickup
High
Low
*
Actual Dropout
High
* Pass/Fail
3
500 W
485 W
515 W
475 W
495 W
P / F
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
BE1-11g
Power (32) Test