Timing verification (3v0 mode) – Basler Electric BE1-11g User Manual

Page 408

background image

396

9424200994 Rev N

Setting

Value

BESTCOMSPlus Screen

Description

Timing Mode

Definite

Protection, Voltage, Undervoltage
(27X-1)

Selects definite timings

27X-1 3V0

Enabled Target Configuration, Targets

Enables 3V0 target for 27X-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 280.

Blocking is disabled.

OUT1 closes for 27X-1 Trip.

OUT2 closes for 27X-1 Pickup.

Fault recording is enabled.

Figure 280. BESTlogicPlus Settings (3V0 Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send

the first row of test settings in Table 140 to the BE1-11g.

Table 140. Pickup Test Settings (3V0 Mode)

Pickup Setting

Time Delay

115 V

50 ms

65 V

50 ms

20 V

50 ms

Step 4: Prepare to monitor the 27X-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 280).

Step 5: Connect and apply a 120 Vac, a single-phase voltage source to terminals C13 (A-phase) and

C16 (Neutral). Reset the target.

Step 6: Slowly decrease the voltage until OUT2 closes and record the pickup. Verify that there is a 27X-

1-3V0 target on the front-panel display. Slowly increase the A-phase voltage until OUT2 opens
and record the reset. Reset the target.

Step 7: Verify the pickup and dropout accuracy at a pickup setting of 65 V and 20 V as listed in Table

140. Record the results.

Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.

Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.

Step 10: (Optional.) Repeat steps 1 through 9 for 27X-2, 27X-3, and 27X-4.

Timing Verification (3V0 Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send

the first row of test settings in Table 141 to the BE1-11g for settings group 0.

Auxiliary Undervoltage (27X) Test

BE1-11g