Terminals Va (C13), Vb (C14), and Vc (C15) are connected in parallel. The single-phase signal is
connected between the parallel group and terminal N (C16).

For single-phase sensing connections derived from a phase-to-phase source:

Terminals Vb (C14), Vc (C15), and N (C16) are connected in parallel. The single-phase signal is
connected between terminal Va (C13) and the parallel group.

Note that the voltage monitor (described below) performs three of three testing for all connections. For
3W and 4W, phases A, B, and C are actually tested. For single-phase connections, the terminals are
connected in parallel as described above and the single-phase is tested three times.

Caution

The Aux VT Connection must be properly selected on the Sensing
Transformers screen in BESTCOMSPlus. Refer to the Configuration
chapter for more information on this setting.

Angle Compensation

Compensation for phase angle differences between the phase and auxiliary VT connections (including
single-phase VTP connections) are possible with the Angle Compensation setting. That is, for a VTP
selection of phase-to-phase and a VTX selection of phase-to-neutral, a value of 30

° should be defined for

angle compensation.

Common system and sensing transformer combinations are shown in Table 11. This table assumes no
step-up or step-down transformer between the two measurement PTs. If the synchronizing zone includes
a step-up or step-down transformer, change the nominal voltages accordingly.

Table 11. Common System and Sensing Transformer Combinations

Phase VT

Connection

Phase

Rotation

Aux VT

Connection

Secondary

Phase Voltage

(Phase-Neutral)

Secondary

Aux Voltage

Angle

Compensation

3-wire

ABC

AB

69.3

120

0

°

3-wire

ABC

BC

69.3

120

240

°

3-wire

ABC

CA

69.3

120

120

°

3-wire

ACB

AB

69.3

120

0

°

3-wire

ACB

BC

69.3

120

120

°

3-wire

ACB

CA

69.3

120

240

°

4-wire

ABC

AN

69.3

69.3

0

°

4-wire

ABC

BN

69.3

69.3

240

°

4-wire

ABC

CN

69.3

69.3

120

°

4-wire

ABC

AB

69.3

120

30

°

4-wire

ABC

BC

69.3

120

270

°

4-wire

ABC

CA

69.3

120

150

°

4-wire

ACB

AN

69.3

69.3

0

°

4-wire

ACB

BN

69.3

69.3

120

°

4-wire

ACB

CN

69.3

69.3

240

°

4-wire

ACB

AB

69.3

120

330

°

4-wire

ACB

BC

69.3

120

90

°

4-wire

ACB

CA

69.3

120

210

°

Sync-Check (25) Protection