beautypg.com

Sync-check verification (25) – Basler Electric BE1-11g User Manual

Page 401

background image

9424200994 Rev N

389

Step

Dropout Delay Setting

Low

Actual Timing

High

Pass/Fail

6

VTP - Dead V Dropout Delay - 5000 ms

4,968 ms

5,032 ms

P / F

6

VTP - Live V Dropout Delay - 5000 ms

4,968 ms

5,032 ms

P / F

7

VTX - Dead V Dropout Delay - 50 ms

18 ms

82 ms

P / F

7

VTX - Live V Dropout Delay - 50 ms

18 ms

82 ms

P / F

7

VTX - Dead V Dropout Delay - 2000 ms

1,968 ms

2,032 ms

P / F

7

VTX - Live V Dropout Delay - 2000 ms

1,968 ms

2,032 ms

P / F

7

VTX - Dead V Dropout Delay - 5000 ms

4,968 ms

5,032 ms

P / F

7

VTX - Live V Dropout Delay - 5000 ms

4,968 ms

5,032 ms

P / F

Sync-Check Verification (25)

Voltage Difference Accuracy =

±2% or ±1 V, whichever is greater

Step

Voltage Difference Setting

Low

Actual

Pickup

High

Actual

Dropout

Pass/Fail

5

VTX - Voltage Difference = 10%

107.8 V

112.2 V

P / F

6

VTP - Voltage Difference = 10%

107.8 V

112.2 V

P / F

Slip Angle Accuracy =

±1°

Step

Slip Angle Setting

Low

Actual

Pickup

High

Actual

Dropout

Pass/Fail

7

Slip Angle = +10°

11°

P / F

7

Slip Angle = –10°

–9°

–11°

P / F

Slip Frequency Accuracy =

±0.01 Hz

Step

Slip Frequency Setting

Low

Actual

Pickup

High

Actual

Dropout

Pass/Fail

8

VTP - Slip Frequency =
59.70 Hz

58.50 Hz

60.89 Hz

P / F

8

VTP - Slip Frequency =
60.30 Hz

59.09 Hz

61.50 Hz

P / F

9

VTX - Slip Frequency =
59.70 Hz

58.50 Hz

60.89 Hz

P / F

9

VTX - Slip Frequency =
60.30 Hz

59.09 Hz

61.50 Hz

P / F

BE1-11g

Sync-Check (25) Test