9424200994 Rev N

53

Figure 43. Sync-Check Settings Screen

Table 13. Operational Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Disabled or Enabled

n/a

n/a

Disabled

Voltage Difference

0 or 1 to 50

1

percent

0

Slip Angle

1 to 99

1

degrees

10

Slip Frequency

0.01 to 0.5

0.01

hertz

0.01

Source Freq > Destination Freq

Disabled or Enabled

n/a

n/a

Disabled

Angle Compensation

0 to 359.9

0.1

degrees

0

25 VM Live Voltage

0 or 10 to 90

1

percent

0

25 VM Dead Voltage

0 or 10 to 90

1

percent

0

25 VM Drop Out Delay

0 or 50 to 60,000

varies

milliseconds

50

25 Voltage Monitor Logic

0 = Disabled

123, 12, 13, 23

n/a

n/a

0

BE1-11g

Sync-Check (25) Protection