Alarms – Basler Electric BE1-11g User Manual
Page 217

9424200994 Rev N
205
Alarms
The BE1-11g monitors internal systems, external interfaces, and power system equipment and
annunciates an alarm when one of these components fail. An alarm can be configured as latching or non-
latching with a status of major or minor. It can also be used as an input to other logic blocks in
BESTlogic
™Plus. Latching alarms are stored in nonvolatile memory and are retained even when BE1-11g
operating power is lost. Active alarms are displayed on the front-panel display, web page interface, and
through BESTCOMSPlus
® until they are cleared. Non-latching alarms are cleared when BE1-11g
operating power is lost.
If an alarm is configured as Major, a front-panel Major Alarm LED lights when the alarm is active. The
front-panel Minor Alarm LED operates in a similar manner. Each alarm provides a logic output that can be
connected to a physical output or other logic input using BESTlogicPlus Programmable Logic.
The ability to program the reporting and display of alarms along with the automatic display priority feature
of the front-panel display gives the BE1-11g the functionality of a local and remote alarm annunciator. See
the
chapter for more information on the automatic display priority logic.
A detailed list of alarms is provided in Table 79.
Table 79. Available Alarms
Name
Description
101 Blocking Tag Status
101 breaker control switch block tag is set
24 Volts Per Hz
Overexcitation
3I0 Demand
Neutral current unbalance demand
43-1 Blocking Tag Status
43-1 virtual switch block tag set
43-2 Blocking Tag Status
43-2 virtual switch block tag set
43-3 Blocking Tag Status
43-3 virtual switch block tag set
43-4 Blocking Tag Status
43-4 virtual switch block tag set
43-5 Blocking Tag Status
43-5 virtual switch block tag set
87 Alarm
Current Differential
Analog
Analog-to-digital converter error
Breaker Fail
Breaker failure
Breaker Monitor 1
Breaker alarm 1 threshold exceeded
Breaker Monitor 2
Breaker alarm 2 threshold exceeded
Breaker Monitor 3
Breaker alarm 3 threshold exceeded
Changes Lost
Password access lost. Read only
Date Time Set
The date/time was set by the user
Defaults Cal Loaded
Remote Module 1 or 2 Alarm
Defaults Loaded
Remote Module 1 or 2 Alarm
DNP Polls Error
DNP polling failure
Ethernet Excess Traffic
Local network overloaded
Ethernet Link Lost
Ethernet communication lost
Fault Report Timeout
True if fault event trigger lasts longer than 60 seconds
Firmware Change
Firmware has been changed
Flash Failure
Remote Module 1 or 2 Alarm
Freq Out Of Range
Frequency is out of range
BE1-11g
Alarms