Breaker control switch (101) test, Functional test procedure – Basler Electric BE1-11g User Manual
Page 555
9424200994 Rev N
543
Breaker Control Switch (101) Test
Functional testing is a way to assess this protection system’s suitability for your application. Functional
testing goes beyond the more basic tests found in acceptance testing, but lacks the detailed function
testing that is part of the commissioning process.
Test each of the following functions to verify that this BE1-11g measures accurately, is within specified
tolerances, and operates correctly. These tests are also suitable for assisting in systematic
troubleshooting in the event that an operation is questioned. Revisiting the test of a specific function can
help verify whether the BE1-11g is operating within specified tolerances. For further assistance, contact
Basler Electric, Technical Sales Support.
Refer to the
chapter for terminal locations and connections.
Reset all targets prior to each test by navigating to the Metering > Status > Targets screen and pressing
the front-panel Reset key. Enter the appropriate username and password if prompted. Clear all logic prior
to each test by using the Settings Explorer in BESTCOMSPlus
® to open the BESTlogic™Plus
Programmable Logic screen and click the Clear button located on the toolbar. After new BESTlogicPlus
settings are made, click the Save button located on the toolbar to compile BESTlogicPlus. Upload
BESTlogicPlus settings by selecting Upload Logic to Device from the Communication pull-down menu.
Operational settings can be sent by selecting Upload Settings to Device from the Communication pull-
down menu or by clicking the Send Settings button on the toolbar.
The actual operating time of an output contact is equal to the recognition time plus the time delay setting
(accuracy) plus 6 milliseconds. Output contact operating time depends upon the type of test set used and
its operating characteristics.
A Functional Test Report is included at the end of this chapter. It should be used to record the results and
verify pickup and timing accuracy.
Refer to the
chapter for more information on this function.
Functional Test Procedure
Step 1: Use BESTCOMSPlus to send the operational settings in Table 247 to the BE1-11g.
Table 247. Operational Settings
Setting
Value
BESTCOMSPlus Screen
Description
101 Mode
Enabled
Control, Breaker Control Switch (101)
Enables 101 function
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure
•
OUT1 closes when 101 Trip output is true.
•
OUT2 closes when 101 TSC output is true.
•
OUT3 closes when 101 Close output is true.
•
OUT4 closes when 101 CSC output is true.
Step 3: Prepare to monitor the 101 breaker control switch operations. Operation can be verified by
monitoring the programmed output contacts on the Metering > Status > Outputs front-panel
display screen.
Step 4: Place the 101 in the TRIP position by using the Metering Explorer in BESTCOMSPlus to open
the Control, Breaker Control Switch tree branch. Click on the TRIP button to select it. Login
may be required. The green selection LED will begin to flash. Within 25 seconds, click on the
TRIP button a second time to operate it. The green selection LED will stop flashing and the trip
status LED will light.
Result: OUT1 closes for 200 ms and returns to the open state. OUT2 closes (TRIP state) and
remains closed.
BE1-11g
Breaker Control Switch (101) Test