Logic connections, Operational settings – Basler Electric BE1-11g User Manual

Page 83

background image

9424200994 Rev N

71

element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.

Logic Connections

Auxiliary overvoltage element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The auxiliary overvoltage element logic block is illustrated in Figure 50. Logic inputs
and outputs are summarized in Table 22.

Figure 50. Auxiliary Overvoltage Element Logic Block

Table 22. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 59X function when true

Trip

Output

True when the 59X element is in a trip condition

Pickup

Output

True when the 59X element is in a pickup condition

Operational Settings

Auxiliary overvoltage element operational settings are configured on the Overvoltage (59X) settings
screen (Figure 51) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 23.

Figure 51. Auxiliary Overvoltage Settings Screen

BE1-11g

Auxiliary Overvoltage (59X) Protection