Basler Electric BE1-11g User Manual
Page 536
524
9424200994 Rev N
Transformers
Aux VT
Connection
AN
System Parameters, Sensing
Transformers
Sets auxiliary VT
connection to AN.
Nominal Phase
Voltage
100 V
System Parameters, Power
System
Sets nominal phase voltage
to 100 V.
Nominal Aux
Voltage
100 V
System Parameters, Power
System
Sets nominal auxiliary
voltage to 100 V.
Element Mode
PLL or
Anticipatory
Control, Synchronizer (25A)
Enables the 25A function.
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in
•
Blocking is disabled.
•
25A is initiated.
•
OUT7 closes for voltage monitor criteria met.
•
Event recording is enabled.
Figure 317. BESTlogicPlus Settings 3 (25A)
Step 3: Use BESTCOMSPlus to open the Control, Synchronizer (25A) screen and send the test settings
in Table 238 to the BE1-11g.
Table 238. Time Pickup Test Settings (25VM)
Setting
Value
Description
25 Voltage Monitor Live
Voltage
90%
Sets live voltage to 90 V (90% of nominal, nominal
= 100 V).
25 Voltage Monitor
Dead Voltage
55%
Sets dead voltage to 55 V (55% of nominal, nominal
= 100 V).
25 Voltage Monitoring
Drop Out Delay
0
Sets drop out delay to 0.
25 Voltage Monitor
Logic
Check boxes as
shown in Figure 318.
Enable: Dead Line/Dead Aux, Dead Line/Live Aux,
Live Line/Dead Aux.
Synchronizer (25A) Test
BE1-11g