Transformers

Aux VT
Connection

AN

System Parameters, Sensing
Transformers

Sets auxiliary VT
connection to AN.

Nominal Phase
Voltage

100 V

System Parameters, Power
System

Sets nominal phase voltage
to 100 V.

Nominal Aux
Voltage

100 V

System Parameters, Power
System

Sets nominal auxiliary
voltage to 100 V.

Element Mode

PLL or
Anticipatory

Control, Synchronizer (25A)

Enables the 25A function.

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in

Figure 317.

Blocking is disabled.

25A is initiated.

OUT7 closes for voltage monitor criteria met.

Event recording is enabled.

Figure 317. BESTlogicPlus Settings 3 (25A)

Step 3: Use BESTCOMSPlus to open the Control, Synchronizer (25A) screen and send the test settings

in Table 238 to the BE1-11g.

Table 238. Time Pickup Test Settings (25VM)

Setting

Value

Description

25 Voltage Monitor Live
Voltage

90%

Sets live voltage to 90 V (90% of nominal, nominal
= 100 V).

25 Voltage Monitor
Dead Voltage

55%

Sets dead voltage to 55 V (55% of nominal, nominal
= 100 V).

25 Voltage Monitoring
Drop Out Delay

0

Sets drop out delay to 0.

25 Voltage Monitor
Logic

Check boxes as
shown in Figure 318.

Enable: Dead Line/Dead Aux, Dead Line/Live Aux,
Live Line/Dead Aux.

Synchronizer (25A) Test

BE1-11g