Group 3 analog input/output parameters – Delta BLD-E1 brushless DC motor drive BLD-E1 Series User Manual
Page 99
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
4-58
Revision May 2009, 00DE, V0.50
Group 3 Analog Input/Output Parameters
This parameter can be set during operation.
03-00
Analog Input 1 (VR)
Factory Setting: 1
03-01
Analog Input 2 (ACI)
Factory Setting: 0
03-02
Analog Input 3 (AVI)
Factory Setting: 0
Settings
VF
VFPG
FOCPM
0: No function
○
○
○
1: Frequency command (torque limit under TQR
control mode)
○
○
○
2: Reserved
3: Preload input
○
○
○
4-6: Reserved
7: Positive torque limit
○
8: Negative torque limit
○
9: Regenerative torque limit
○
10: Positive/negative torque limit
○
When it is frequency command or TQR speed limit, the corresponding value for 0~±
10V/4~20mA is 0 – max. output frequency(Pr.01-00)
When it is torque command or torque limit, the corresponding value for 0~±10V/4~20mA is
0 – max. output torque (Pr.07-14).
When it is torque compensation, the corresponding value for 0~±10V/4~20mA is 0 – rated
torque.