Group 3 Analog Input/Output Parameters

This parameter can be set during operation.

03-00

Analog Input 1 (VR)

Factory Setting: 1

03-01

Analog Input 2 (ACI)

Factory Setting: 0

03-02

Analog Input 3 (AVI)

Factory Setting: 0

Settings

VF

VFPG

FOCPM

0: No function

1: Frequency command (torque limit under TQR
control mode)

2: Reserved

3: Preload input

4-6: Reserved

7: Positive torque limit

8: Negative torque limit

9: Regenerative torque limit

10: Positive/negative torque limit

When it is frequency command or TQR speed limit, the corresponding value for 0~±

10V/4~20mA is 0 – max. output frequency(Pr.01-00)

When it is torque command or torque limit, the corresponding value for 0~±10V/4~20mA is

0 – max. output torque (Pr.07-14).

When it is torque compensation, the corresponding value for 0~±10V/4~20mA is 0 – rated

torque.