Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
4-52
Revision May 2009, 00DE, V0.50
Settings
Functions
Descriptions
27 ASR1/ASR2
selection
ON: speed will be adjusted by ASR 2 setting.
OFF: speed will be adjusted by ASR 1 setting.
28
Emergency stop (EF1)
(Motor coasts to stop)
When it is ON, the drive will execute emergency stop
with fault code 50 (EF1)
29-30 Reserved
31 High
torque
bias
32 Middle
torque
bias
33
Low torque bias
When Pr.07-19 is set to 3:
31: The high torque bias is according to the Pr.07-21
setting.
32: The middle torque bias is according to the Pr.07-22
setting.
33: The low torque bias is according to the Pr.07-23
setting.
31 32 33 Torque
Bias
OFF OFF OFF
No
OFF OFF ON
07-23
OFF ON OFF
07-22
OFF ON ON
07-23+07-22
ON OFF
OFF
07-21
ON OFF ON
07-21+07-23
ON ON
OFF 07-21+07-22
ON ON ON
07-21+07-22+07-23
34-37 Reserved
38
Disable write EEPROM
function
When this function is enabled, you can’t write into
EEPROM.
39 Reserved
40
Enable drive function
When this function is enabled, the drive function can be
executed. This function can be used with multi-function
output (setting Pr.02-11~Pr.02-14 to 15) and (Pr.02-31
and Pr.02-32).
02-05
Reserved
02-06
Reserved
02-07
Reserved
02-08
Reserved