Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
4-42
Revision May 2009, 00DE, V0.50
Group 01 Basic Parameters
This parameter can be set during operation.
01-00
Maximum Output Frequency
Control
mode
VF
VFPG
FOCPM
Factory setting: 3000(250)
Settings
120~4000rpm
(10~400z)
This parameter determines the brushless DC motor drive’s Maximum Output Frequency. All
the brushless DC motor drive frequency command sources (analog frequency inputs 0 to
+10V and 4 to 20mA) are scaled to correspond to the output frequency range.
01-01
1st Output Frequency Setting
Control
mode
VF
VFPG
FOCPM
Factory setting: 60.00
Settings
0.00~400.00Hz
It is for the base frequency and motor rated frequency.
This value should be set according to the rated frequency of the motor as indicated on the
motor nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it
should be set to 50Hz.
01-02
1st Output Voltage Setting
Control
mode
VF
VFPG
FOCPM
Settings 230V series 0.1 to 255.0V Factory
Setting:
220.0
460V series 0.1 to 510.0V Factory
Setting:
440.0
It is for the base frequency and motor rated frequency.
This value should be set according to the rated voltage of the motor as indicated on the motor
nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be
set to 200.0.
There are many motor types in the market and the power system for each country is also
difference. The economic and convenience method to solve this problem is to install the
brushless DC motor drive. There is no problem to use with the different voltage and frequency
and also can amplify the original characteristic and life of the motor.