Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series

4-50

Revision May 2009, 00DE, V0.50

Settings VF

VFPG

FOCPM

33: Low torque bias (by Pr.07-23)

34-37: Reserved

38: Disable EEPROM write function

39

:Reserved

40

:Enable drive to function

This parameter selects the functions for each multi-function terminal.

If Pr.02-00 is set to 3-wire operation control. Terminal MI1 is for STOP terminal. Therefore,

MI1 is not allowed for any other operation.

Settings

Functions

Descriptions

0 No

Function

1

Multi-step speed
command 1

2

Multi-step speed
command 2

3

Multi-step speed
command 3

15 step speeds could be conducted through the digital
statuses of the 4 terminals, and 17 in total if the master
speed and JOG are included. (Refer to Pr. 04-00~04-15)

4

Multi-step speed
command 4

When using communication to control the multi-step

speed, setting 1 to 4 will be invalid.

5 Reset

After the error of the drive is eliminated, use this
terminal to reset the drive.

6 Reserved

7

Acceleration/deceleration
Speed Inhibit

When this function is enabled, acceleration and
deceleration is stopped and the brushless DC motor
drive starts to accel./decel. from the inhibit point.