Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series

4-2

Revision May 2009, 00DE, V0.50

4.1 Summary of Parameter Settings

Group 00 System Parameters

: The parameter can be set during operation.

Parameter

Explanation

Settings

Factory

Setting

VF VFPG FOCPM

00.00

Identity Code of

the Brushless DC

Motor Drive

0

:115V,1PH,0.2KW,1/4HP

2

:115V,1PH,0.4KW,1/2HP

4

:115V,1PH,0.7KW,1HP

0

:230V,1PH,0.2KW,1/4HP

2

:230V,1PH,0.4KW,1/2HP

4

:230V,1PH,0.7KW,1HP

6

:230V,1PH,1.5KW,2HP

8

:230V,1PH,2.2KW,3HP

0

:230V,3PH,0.2KW,1/4HP

2

:230V,3PH,0.4KW,1/2HP

4

:230V,3PH,0.7KW,1HP

6

:230V,3PH,1.5KW,2HP

8

:230V,3PH,2.2KW,3HP

10

:230V,3PH,3.7KW,5HP

3

:460V,3PH,0.4KW,1/2HP

5

:460V,3PH,0.7KW,1HP

7

:460V,3PH,1.5KW,2HP

9

:460V,3PH,2.2KW,3HP

11

:460V,3PH,3.7KW,5HP

Read-

only

00.01 Rated

Current

Display of the

Brushless DC

Motor Drive

Display according to the model

series

Read-

only

00.02 Parameter

Reset

0

:No function

10

:All parameters are reset to

factory settings

0

00.03 Start-up

Display

Selection

0

:Frequency command

1

:Out put frequency

2

:DC BUS voltage

3

:Output current

4

:output voltage

0