Chapter 4 Parameters| BLD-E1 Series
Revision May 2009, 00DE, V0.50
4-17
Parameter
Explanation Settings
Factory
Setting
VF VFPG FOCPM
Detection Time
(OT1)
06.08 Over-torque
Detection Selection
(OT2)
0: disable
1: over-torque detection during
constant speed operation, continue
to operate after detection
2: over-torque detection during
constant speed operation, stop
operation after detection
3: over-torque detection during
operation, continue to operate after
detection
4: over-torque detection during
operation, stop operation after
detection
0
○
○
○
06.09 Over-torque
Detection Level
(OT2)
10~250% 150
○
○
○
06.10 Over-torque
Detection Time
(OT2)
0.0~60.0 sec
0.1
○
○
○
06.11 Current
Limit
0~250%
200 ○ ○
○
06.12 Electronic
Thermal
Relay Selection
0: Inverter motor
1: Standard motor
2: Disable
2
○
○
○
06.13 Electronic
Thermal
Characteristic
30.0~600.0 sec
60.0
○
○
○
06.14 Heat
Sink
Over-
heat (OH) Warning
0.0~110.0℃ 85.0
○
○
○
06.15 Stall
Prevention
Limit Level
0
~100% (refers to Pr. 06-02, 06-03) 50
○
○
○
06.16 Present
Fault
Record
0: No fault
0
○
○
○
06.17
Second Most
1: Over-current during acceleration
0
○
○
○