Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-17

Parameter

Explanation Settings

Factory

Setting

VF VFPG FOCPM

Detection Time

(OT1)

06.08 Over-torque

Detection Selection

(OT2)

0: disable

1: over-torque detection during

constant speed operation, continue

to operate after detection

2: over-torque detection during

constant speed operation, stop

operation after detection

3: over-torque detection during

operation, continue to operate after

detection

4: over-torque detection during

operation, stop operation after

detection

0

06.09 Over-torque

Detection Level

(OT2)

10~250% 150

06.10 Over-torque

Detection Time

(OT2)

0.0~60.0 sec

0.1

06.11 Current

Limit

0~250%

200 ○ ○

06.12 Electronic

Thermal

Relay Selection

0: Inverter motor

1: Standard motor

2: Disable

2

06.13 Electronic

Thermal

Characteristic

30.0~600.0 sec

60.0

06.14 Heat

Sink

Over-

heat (OH) Warning

0.0~110.0℃ 85.0

06.15 Stall

Prevention

Limit Level

0

~100% (refers to Pr. 06-02, 06-03) 50

06.16 Present

Fault

Record

0: No fault

0

06.17

Second Most

1: Over-current during acceleration

0