Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series

5-6

Revision May 2009, 00DE, V0.50

5.9 Motor cannot Run

Motor c annot run

Check if
keypad display
is normal

No

No

No

No

No

No

No

No

No

No

No

No

No

No

Check if non-fuse
breaker and magnetic
contactor are O N

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Set them to ON

Reset after c learing
fault and then RUN

Check if there i s any
fault code di splayed

Check if input
voltage is normal

Check if any faults
occur, such as
Lv, P HL or di sconnection

Input "RUN"
command
by keypad

It can run when
no faults oc cur

Pres s RUN k ey to
check if it can run

Maybe brushless DC motor drive has malfunction or
misoperation due to noise. P lease contact DELTA.

Pres s UP key to
set frequency

Yes

Modify operation
speed

Check if input FWD
or REV c ommand

Check if the wiri ng
between MI1 and
MI2-DCM is correct

Yes

Change switch or relay

Set s peed or not

Pres s UP to
check if motor
can run

Correc t connection

Check if the parameter
setting and wiring of
analog si gnal and
multi-s tep speed
are correct

No

Motor has malfunction

No

Maybe brushless DC motor drive has
malfunction. Please contac t DELTA.

Check if there i s any
output voltage from
terminals U, V and W

Check if motor
connection i s c orrect

No

Connec t correctly

Check if the setting
of torque
compens ati on
is correct

Increase the setting of
torque c ompensation

Motor i s l oc ked due to large l oad, pl eas e reduce load.
For example, if there i s a brake, c hec k if it is releas ed.

If load i s too l arge

if upper bound speed
and setting freq. is
lower than the min.
output speed

Yes

Change defec tiv e
potentiometer and
relay

Yes