Group 6: protection parameters – Delta BLD-E1 brushless DC motor drive BLD-E1 Series User Manual
Page 57
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
4-16
Revision May 2009, 00DE, V0.50
Group 6: Protection Parameters
: The parameter can be set during operation.
Parameter
Explanation Settings
Factory
Setting
VF VFPG FOCPM
06.00
Low Voltage Level 160.0~220.0Vdc
320.0~440.0Vdc
180.0
360.0
○
○
○
06.01 Phase-loss
Protection
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
2
○
○
○
06.02 Over-current
Stall
Prevention during
Acceleration
00: disable
00~250%
00
○
○
06.03 Over-current
Stall
Prevention during
Operation
00: disable
00~250%
00
○
○
06.04 Accel./Decel.
Time
Selection of Stall
Prevention at
constant speed
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel time
0
○
○
06.05 Over-torque
Detection Selection
(OT1)
0: disable
1: over-torque detection during
constant speed operation, continue
to operate after detection
2: over-torque detection during
constant speed operation, stop
operation after detection
3: over-torque detection during
operation, continue to operate after
detection
4: over-torque detection during
operation, stop operation after
detection
0
○
○
○
06.06 Over-torque
Detection Level
(OT1)
10~250% 150
○
○
○
06.07 Over-torque
0.0~60.0 sec
0.1
○
○
○