Group 6: protection parameters – Delta BLD-E1 brushless DC motor drive BLD-E1 Series User Manual

Page 57

background image

Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series

4-16

Revision May 2009, 00DE, V0.50

Group 6: Protection Parameters

: The parameter can be set during operation.

Parameter

Explanation Settings

Factory

Setting

VF VFPG FOCPM

06.00

Low Voltage Level 160.0~220.0Vdc

320.0~440.0Vdc

180.0

360.0

06.01 Phase-loss

Protection

0: Warn and keep operation

1: Warn and ramp to stop

2: Warn and coast to stop

2

06.02 Over-current

Stall

Prevention during

Acceleration

00: disable

00~250%

00

06.03 Over-current

Stall

Prevention during

Operation

00: disable

00~250%

00

06.04 Accel./Decel.

Time

Selection of Stall

Prevention at

constant speed

0: by current accel/decel time

1: by the 1st accel/decel time

2: by the 2nd accel/decel time

3: by the 3rd accel/decel time

4: by the 4th accel/decel time

5: by auto accel/decel time

0

06.05 Over-torque

Detection Selection

(OT1)

0: disable

1: over-torque detection during

constant speed operation, continue

to operate after detection

2: over-torque detection during

constant speed operation, stop

operation after detection

3: over-torque detection during

operation, continue to operate after

detection

4: over-torque detection during

operation, stop operation after

detection

0

06.06 Over-torque

Detection Level

(OT1)

10~250% 150

06.07 Over-torque

0.0~60.0 sec

0.1