Group 6 Protection Parameters

This parameter can be set during operation.

06-00

Low Voltage Level

Control

mode

VF

VFPG

FOCPM

Settings

230V

series

160.0~220.0Vdc

Factory Setting: 180.0

460V series 320.0~440.0Vdc

Factory Setting: 360.0

It is used to set the Lv level.

LV

Pr. 06-00

30V(60V)

input voltage

06-01

Phase-loss Protection

Control

mode

VF

VFPG

FOCPM

Factory setting: 2

Settings

0

Warn and keep operation

1

Warn and ramp to stop

2

Warn and coast to stop

It is used to set the phase-loss treatment. The phase-loss will effect drive’s control

characteristic and life.

06-02

Over-Current Stall Prevention during Acceleration

Control

mode

VF

VFPG

Factory setting: 00

Settings

00:

disable

00~250%

During acceleration, the AC drive output current may increase abruptly and exceed the value

specified by Pr.06-02 due to rapid acceleration or excessive load on the motor. When this

function is enabled, the AC drive will stop accelerating and keep the output frequency

constant until the current drops below the maximum value.