Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-87

3.4 Check sum

ASCII mode:

LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the

values of the bytes from ADR1 to last data character then calculating the hexadecimal

representation of the 2’s-complement negation of the sum.

For example, reading 1 word from address 0401H of the AC drive with address 01H.

STX ‘:’

‘0’

Address 1
Address 0

‘1’
‘0’

Function 1
Function 0

‘3’
‘0’
‘4’
‘0’

Starting data address

‘1’
‘0’
‘0’
‘0’

Number of data

‘1’

‘F’

LRC Check 1
LRC Check 0

‘6’

CR

END 1
END 0

LF

01H+03H+04H+01H+00H+01H=0AH, the 2’s-complement negation of 0AH is F6H.

RTU mode:

Address

01H

Function

03H
21H

Starting data address

02H
00H

Number of data
(count by word)

02H

CRC CHK Low

6FH

CRC CHK High

F7H

CRC (Cyclical Redundancy Check) is calculated by the following steps:

Step 1:

Load a 16-bit register (called CRC register) with FFFFH.

Step 2:

Exclusive OR the first 8-bit byte of the command message with the low order byte

of the 16-bit CRC register, putting the result in the CRC register.

Step 3:

Examine the LSB of CRC register.

Step 4:

If the LSB of CRC register is 0, shift the CRC register one bit to the right with MSB

zero filling, then repeat step 3. If the LSB of CRC register is 1, shift the CRC register one bit

to the right with MSB zero filling, Exclusive OR the CRC register with the polynomial value

A001H, then repeat step 3.