Chapter 2 Installation and Wiring| BLD-E1 Series

2-8

Revision May 2009, 00DE, V0.50

„

When using a general GFCI (Ground Fault Circuit Interrupter), select a current sensor

with sensitivity of 200mA or above, and not less than 0.1-second operation time to avoid

nuisance tripping. For the specific GFCI of the brushless DC motor drive, please select a

current sensor with sensitivity of 30mA or above.

Output terminals for main circuit (U, V, W)

„

The factory setting of the operation direction is forward running.

„

When it needs to install the filter at the output side of terminals U/T1, V/T2, W/T3 on the

brushless DC motor drive. Please use inductance filter. Do not use advanced capacitors

or L-C (Inductance-Capacitance) or R-C (Resistance-Capacitance), unless approved by

Delta.

„

DO NOT connect advanced capacitors or surge absorbers at the output terminals of

brushless DC motor drives.

„

Use

well-insulated

motor,

suitable for drive operation.

„

When using a general GFCI (Ground Fault Circuit Interrupter), select a current sensor

with sensitivity of 200mA or above, and not less than 0.1-second operation time to avoid

nuisance tripping. For the specific GFCI of the brushless DC motor drive, please select a

current sensor with sensitivity of 30mA or above.

Terminals [+, -] for connecting brake resistor

„

Connect a brake resistor or brake unit in applications with frequent decelerations, short

deceleration time, insufficient brake torque or requiring increased brake torque.

„

When using external brake unit, please connect it to the terminals [+, -]. Please do NOT

connect brake resistors to terminals [+, -] directly, as it may cause damage.

„

All BLD-E1 series don’t have a built-in brake chopper. Please connect an external

optional brake unit (BUE-series) and brake resistor.

„

When not used, please leave the terminals [+, -] open.