Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-55

Settings

Functions

Descriptions

0 No

Function

1

AC Drive Operational

Active when there is an output from the drive or RUN
command is ON.

2 Operation

speed

attained

Active when the brushless DC motor drive reaches the output
frequency setting.

3

Desired Frequency
Attained 1 (Pr.02-25, 02-
26)

Active when the desired frequency (Pr.02-25, 02-26) is
attained.

4

Desired Frequency
Attained 2 (Pr.02-27, 02-
28)

Active when the desired frequency (Pr.02-27, 02-28) is
attained.

5

Zero Speed (frequency
command)

Active when frequency command =0. (the drive should be at
RUN mode)

6

Zero Speed with Stop
(frequency command)

Active when frequency command =0 or stop.

7 Over

Torque

(OT1)

Active when detecting over-torque. Refer to Pr.06-05 (over-
torque detection selection-OT1), Pr.06-06 (over-torque
detection level-OT1) and Pr.06-07 (over-torque detection
time-OT1). (Pr.06-05~06-07)

8 Over

Torque

(OT2)

Active when detecting over-torque. Refer to Pr.06-08 (over-
torque detection selection-OT2), Pr.06-09 (over-torque
detection level-OT2) and Pr.06-10 (over-torque detection
time-OT2). (Pr.06-08~06-10)

9 Drive

Ready

Active when the drive is ON and no abnormality detected.

10

User-defined Low-
voltage Detection

Active when the DC Bus voltage is too low. (refer to Pr.06-00
low voltage level)

11 Malfunction

Indication

Active when fault occurs (except Lv stop).

12 Reserved

13 Overheat

(Pr.06-14)

Active when IGBT or heat sink overheats to prevent OH turn
off the drive. (refer to Pr.06-14)

14~16 Reserved

17

Malfunction indication 1 Activate after 10ms when fault occurs (except Lv stop).

18~19 Reserved

20 Warning

Output

Active when the warning is detected.

21 Over-voltage

Warning

Active when the over-voltage is detected.