Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-69

06-16

Present Fault Record

06-17

Second Most Recent Fault Record

06-18

Third Most Recent Fault Record

06-19

Fourth Recent Fault Record

06-20

Fifth Most Recent Fault Record

06-21

Sixth Most Recent Fault Record

Control

mode

VF

VFPG

FOCPM

Factory setting: 0

Readings

0

No

fault

1

Over-current during acceleration (ocA)

2

Over-current during deceleration (ocd)

3

Over-current

during constant speed (ocn)

4

Ground

fault

(GFF)

5

Reserved

6

Over-current at stop (ocS)

7

Over-voltage during acceleration (ovA)

8

Over-voltage during deceleration (ovd)

9

Over-voltage during constant speed (ovn)

10

Over-voltage at stop (ovS)

11

Low-voltage during acceleration (LvA)

12

Low-voltage during deceleration (Lvd)

13

Low-voltage during constant speed (Lvn)

14

Low-voltage at stop (LvS)

15

Phase loss (PHL)

16

IGBT heat sink over-heat (oH1)

17

heat sink over-heat 40HP above (oH2)

18

TH1 open loop error (tH1o)

19

Reserved

20

Reserved

21

Over-load (oL) (150% 1Min)

22

Motor over-load (EoL1)

23

Reserved

24

Reserved

25

Reserved

26

Over-torque

1

(ot1)

27

Over-torque

1

(ot2)