00-02
Parameter Reset
Control
mode
VF
VFPG
FOCPM
Factory setting: 0
Settings
0
No
Function
10 All parameters are reset to factory settings
When it is set to 10, all parameters will be reset to factory settings.
00-03
Start-up Display Selection
Control
mode
VF
VFPG
FOCPM
Factory setting: 0
Settings 0
Display the frequency command value. (F)
1
Display the actual output frequency (H)
2
DC BUS voltage (V)
3
Display the output current (A)
4
Output voltage (E)
5
Multifunction display, see Pr.00-04
This parameter determines the start-up display page after power is applied to the drive. User
defined options are displayed according to Pr.00-04.
00-04
Content of Multi-Function Display
Control
mode
VF
VFPG
FOCPM
Factory setting: 0
Settings 0 Display the output current in A supplied to the motor
1
Reserved
2 Display actual output frequency (H)
3
Display the actual DC BUS voltage in VDC of the
brushless DC motor drive (U)
4
Display the output voltage in VAC of terminals U, V,
W to the motor (E)
5
Display the power factor angle in º of terminals U, V,
W to the motor (n.)
6
Display the output power in kW of terminals U, V
and W to the motor (kW)
7
Display the actual motor speed in rpm (enabled
when using with PG card).
8
Display the estimated value of torque in % as it
relates to current.
9 Display PG position