Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-53

02-09

Digital Input Response Time

Control

mode

VF

VFPG

FOCPM

Factory setting: 0.005

Settings

0.001~ 30.000 sec

This parameter is used for digital input terminal signal delay and confirmation. The delay time

is confirmation time to prevent some uncertain interferences that would result in error (except

for the counter input) in the input of the digital terminals (FWD, REV and MI1~6). Under this

condition, confirmation for this parameter could be improved effectively, but the response time

will be somewhat delayed.

02-10

Digital Input Operation Direction

Control

mode

VF

VFPG

FOCPM

Factory setting: 0

Settings

0 ~ 65535

This parameter is used to set the input signal level and it won’t be affected by the

SINK/SOURCE status.

Bit0 is for FWD terminal, bit1 is for REV terminal and bit2 to bit9 is for MI1 to MI8.

User can change terminal status by communicating.

For example, MI1 is set to 1 (multi-step speed command 1), MI2 is set to 2 (multi-step speed

command 2). Then the forward + 2

nd

step speed command=1001(binary)=9 (Decimal). Only

need to set Pr.02-10=9 by communication and it can forward with 2

nd

step speed. It doesn’t

need to wire any multi-function terminal.

bit5 bit4 bit3 bit2 bit1 bit0

MI6 MI5 MI4 MI3 MI2 MI1

02-11

Reserved

02-12

Reserved

02-13

Multi-function Output 3 (MO1)

02-14

Multi-function Output 4 (MO2)

Factory Setting: 0

Settings

VF VFPG

FOCPM

0

:No function

1: Operation indication

2: Operation speed attained