Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series

4-72

Revision May 2009, 00DE, V0.50

Group 7 Special Parameters

This parameter can be set during operation.

07-00

Reserved

07-01

Reserved

07-02

DC Brake Current Level

Control

mode

VF

VFPG

Factory Setting: 0.0

Settings

0

to

100%

This parameter sets the level of DC Brake Current output to the motor during start-up and

stopping. When setting DC Brake Current, the Rated Current (Pr.00-01) is regarded as 100%.

It is recommended to start with a low DC Brake Current Level and then increase until proper

holding torque has been attained.

When it is FOCPM mode, it can enable DC brake function by setting to any value.

07-03

DC Brake Time during Start-up

Control

mode

VF

VFPG

FOCPM

Factory Setting: 0.0

Settings

0.0 to 60.0 sec

This parameter determines the duration of the DC Brake current after a RUN command.

07-04

DC Brake Time during Stopping

Control

mode

VF

VFPG

FOCPM

Factory Setting: 0.0

Settings

0.0 to 60.0 sec

This parameter determines the duration of the DC Brake current during stopping.

07-05

Start-Point for DC Brake

Control

mode

VF

VFPG

Factory Setting: 0

Settings

0.00

to

48000rpm

This

parameter

determines

the frequency when DC Brake will begin during deceleration.

When the setting is less than start frequency (Pr.01-09), start-point for DC brake will begin

from the min. frequency.