Chapter 4 Parameters| BLD-E1 Series

Revision May 2009, 00DE, V0.50

4-65

06-02
Over-Current
Detection
Level

Output

Frequency

Over-Current Stall

prevention during

Acceleration,

frequency held

time

actual acceleration time when over-current stall

prevention is enabled

current

06-03

Over-current Stall Prevention during Operation

Control

mode

VF

VFPG

Factory setting: 00

Settings

00: disable
00 to 250%

If the output current exceeds the setting specified in Pr.06-03 when the drive is operating, the

drive will decrease its output frequency by Pr.06-04 setting to prevent the motor stall. If the

output current is lower than the setting specified in Pr.06-03, the drive will accelerate (by

Pr.06-04) again to catch up with the set frequency command value.

Over-Current
Detection Level
06-03

Output Current

Output
Frequency

Over-Current Stall
Prevention during
Operation, output
frequency decrease

over-current stall prevention during operation

Time

06-04

Accel./Decel. Time Selection of Stall Prevention at constant speed

Control

mode

VF

VFPG

Factory setting: 0

Settings

0

by current accel/decel time

1

by the 1st accel/decel time

2

by the 2nd accel/decel time

3

by the 3rd accel/decel time

4

by the 4th accel/decel time

5

by auto accel/decel time